Model Number: ASD800
Brand Name: ANALOGSYSTEMS
Key Specifications/Special Features:
IntroductionASD800 dust concentration meter combines electrostatic induction principle with microprocessor technology, so that with great property of fast data process, high interference resistance, well reliability and high accuracy. Adopting advanced HART communication and output 4-20mA signal, which greatly assist local data collection and parameter configuration, meanwhile, liquid crystal display and buttons are convenient to read data and maintain the scene. It can be applied in detecting various sack-duster leaking and monitoring dust concentration of exit.FeaturesInstall easily
Measuring small granules
Measuring range extensively
Easily collect various kinds of output signals
Liquid crystal display and buttons to operate easily
No need to keeping clean according to optic window
Granules on detector do not affect measuring
Measuring medium: suspended solid granules in the airflow
Dust granule: ≥0.3μm
Measuring range: 0.1~100mg/m
3Accuracy: ±10%
Temperature: 200℃(Standard)
Pressure: 1.4MPa(Standard)
Flue gas flow speed: <4m/s
Humidity: ≤95%RH(non-condensing)
Power supply: DC 24V
Output signal: 4~20mA current signal, HART communication
Monitoring dedusting efficiency(The monitoring and optimal control of dedusting efficiency)
Monitoring flue pipe dust
Monitoring flue release dust
Monitoring dedusting
Recycle cement by cement rotary kiln
Detecting sack leaking